Specifications – Rockwell Automation 1792D-8BIO8E ArmorBlock MaXum 8 Input/8 Output Module Series B Manuel d'utilisation
Page 11

ArmorBlock MaXum 8 Input/8 Output Module Series B 11
Publication 1792D-IN033B-EN-P - September 2000
Specifications
8 Input / 8 Output Module - Cat. No. 1792D-8BIO8E
Sinking Input Specifications
Max.
Min.
Inputs per block
8 - 3 wire or dry contact PNP devices
Sensor Source Current (per
connector)
100mA total
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
-
Off-state Current
-
1.5mA
Output Specifications
Max.
Min.
Outputs per block
8 sourcing outputs
Off Peak Blocking Voltage
30V
10V
On-state Voltage Drop
1V
-
On-state Current
0.3A
-
Off-state Leakage
1.5mA
-
Module Current (all outputs)
2.4A
-
Surge Current - for 10 ms,
repeatable every 2s
0.6A
-
General Specifications
Indicators
Net/Mod Status - red/green
Logic Status - red/green
Point LED - yellow/orange/red
Communication Rate
•
125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
•
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
•
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)
DeviceNet Power: Fully loaded
Varies depending on number and
current draw of attached sensors
and actuators
Voltage
Current
25V dc max
150mA
11V dc min
3A (8 inputs @ 50mA
and 8 outputs @
300mA)
Dimensions (assembled to base)
inches - (Millimeters)
1.9H x 2.7w x6.85D
(48.26)H x (68.6)W x (174)D (millimeters)