Specifications – Rockwell Automation 1792D-8BIO8E ArmorBlock MaXum 8 Input/8 Output Module Series B Manuel d'utilisation

Page 11

Advertising
background image

ArmorBlock MaXum 8 Input/8 Output Module Series B 11

Publication 1792D-IN033B-EN-P - September 2000

Specifications

8 Input / 8 Output Module - Cat. No. 1792D-8BIO8E

Sinking Input Specifications

Max.

Min.

Inputs per block

8 - 3 wire or dry contact PNP devices

Sensor Source Current (per
connector)

100mA total

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Output Specifications

Max.

Min.

Outputs per block

8 sourcing outputs

Off Peak Blocking Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.3A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

2.4A

-

Surge Current - for 10 ms,
repeatable every 2s

0.6A

-

General Specifications

Indicators

Net/Mod Status - red/green
Logic Status - red/green
Point LED - yellow/orange/red

Communication Rate

125Kbps @ 500 meters(1600 feet) for thick cable,

flat media length 375 meters (1230 feet)

250Kbps @ 200 meters(600 feet) for thick cable,

flat media length 150 meters (492 feet)

500Kbps @ 100 meters (330 feet) for thick cable,

flat media length 75 meters (246 feet)

DeviceNet Power: Fully loaded
Varies depending on number and
current draw of attached sensors
and actuators

Voltage
Current

25V dc max
150mA

11V dc min
3A (8 inputs @ 50mA
and 8 outputs @
300mA)

Dimensions (assembled to base)
inches - (Millimeters)

1.9H x 2.7w x6.85D
(48.26)H x (68.6)W x (174)D (millimeters)

Advertising