Connect the cord sets to the maxum module – Rockwell Automation 1792D-8BIO8E ArmorBlock MaXum 8 Input/8 Output Module Series B Manuel d'utilisation
Page 5

ArmorBlock MaXum 8 Input/8 Output Module Series B 5
Publication 1792D-IN033B-EN-P - September 2000
Note: Dimensions change according to the cable base and module
combination used.
Connect the Cord Sets to the MaXum Module
This module uses 5 pole micro (12mm) style PCB mounted
connectors.
Eight micro caps cover the connectors on your module. Remove the
caps and connect your cables to the appropriate ports. This product
has one input and one output per I/O connector.
Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown next.
Please refer to publication 889-5.0 for Rockwell Automation cables
and cord sets offerings.
Align the
screws to
properly
assemble the
module to the
base.
Cable Base 1792D-CBFM is
used for this example.
41942
Assembled
dimensions in (mm)
1.9(48.26)
2.7 (68.6)
6.85 (174mm)
41452
Input/ Output Micro-Connector
(View into Socket)
Pin 1 Sensor Source Voltage
Pin 2 Input B
Pin 3 Return Logic Ground
1
Pin 4 Input A
Pin 5 Not Used
1Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.