Connect 1/4" water supply tube to brass filter at inlet of solenoid. DO
NOT USE PLASTIC TUBING IN CONTACT WITH ANY HOT
PLENUM SURFACE OR DUCT. IF USING PLASTIC TUBING, USE
TUBE SUPPORT P189 AND PLASTIC COMPRESSION SLEEVE
P190.

Turn damper knob to winter (open) position. Turn on water
supply and check operation of humidifier. Set humidistat to a demand
setting. With the furnace off, the solenoid valve should be closed.
Start the furnace, the solenoid valve should open when the blower or
burner circuit is energized. Check flow of water through distributor
trough and evaporator pad. The standard GA4231 yellow orifice will
supply approximately 3.5 GPH of water at a line water pressure of 60
psi. For low water pressures (20-40 psi) a larger orange orifice
GA4299 is available to provide the same flow. Leave humidistat set
at the recommended setting.

Connect drain hose to 1/2" spout on humidifier cabinet using hose
clamp. Run 1/2" hose to suitable drain such as floor drain, sewer or
laundry sink. Be sure hose has continuous slope and is not kinked at
any point.

6

5

WIRE JUMPER

7A

7C

7B

7D

7

(HOT)

115v.

60CY.

ON-OFF SWITCH

COMMON LEAD

FURNACE

C

HI
LO

GA50

CURRENT

SENSING

RELAY

MULTI
SPEED
BLOWER
MOTOR

AC L

AC N

HUM

SNSR

24V. SOLENOID VALVE

727-58 24 V. TRANSFORMER

(HOT)

C

115v.
60CY.

ON-OFF SWITCH

AC L

AC N

HUM

SNSR

24V. SOLENOID VALVE

727-58 24 V. TRANSFORMER

L1

C

NO

(HOT)

L2

115v.
60CY.

ON-OFF SWITCH

12500 AIR

PRESSURE SWITCH

AC L

AC N

HUM

SNSR

24V. SOLENOID VALVE

727-58 24 V. TRANSFORMER

R

FURNACE

CONTROL BOARD

C

24v.
60CY.

AC L

AC N

HUM

SNSR

24V. SOLENOID VALVE

FURNACE

BOARD

W

WIRE JUMPER

OUTDOOR TEMP. SENSOR

OUTDOOR TEMP. SENSOR

OUTDOOR TEMP. SENSOR

OUTDOOR TEMP. SENSOR

N

W 24v.

60CY.

ACC
EAC

(HOT)

C

115v.
60CY.

ON-OFF SWITCH

COMMON LEAD

FURNACE

C

HI
LO

GA50

CURRENT

SENSING

RELAY

MULTI
SPEED
BLOWER
MOTOR

24V. SOLENOID VALVE

HUMIDISTAT

24 V. TRANSFORMER

(HOT)

C

115v.
60CY.

ON-OFF SWITCH

24V. SOLENOID VALVE

24V. SOLENOID VALVE

24 V. TRANSFORMER

L1

C

NO

(HOT)

L2

115v.
60CY.

ON-OFF SWITCH

12500 AIR

PRESSURE SWITCH

24 V. TRANSFORMER

HUM

FURNACE

CONTROL BOARD

C

24v.
60CY.

24V. SOLENOID VALVE

HUMIDISTAT

HUMIDISTAT

HUMIDISTAT

FURNACE

BOARD

7E

7G

7F

7H

7A-7D Electronic Humidistat

7A - To furnace control board 24 volts
7B - To constant power using 24V transformer and pressure switch
7C - To furnace control board 115 volts with 24V transformer
7D - To constant power using 24V relay and current sensing relay

7E-7H Manual Humidistat

7E - To furnace control board 24 volts
7F - To constant power using 24V transformer and pressure switch
7G - To furnace control board 115 volts with 24V transformer
7H - To constant power using 24V relay and current sensing relay

WIRE

JUMPER

WIRE

JUMPER

WIRE

JUMPER

GCV3412 CODE VALVE INSTALLATION INSTRUCTIONS

Copper Pipe
1. Turn off water supply.
2. Clean pipe, fittings and valve with sandpaper or wire brush.
3. Apply a thin layer of flux to all surfaces to be soldered.
4. Assemble valve to pipe and/or fittings.
5. Cooling the valve by wrapping a wetted rag around the valve is
optional.
6. Heat the joints with a torch. Apply solder to each joint. Continue to
apply heat sufficient to keep solder liquid.
7. After solder has filled entire joint area, remove heat and allow joint
to cool. Do not move or disturb.
8. Slide compression nut over 1/4” copper tube followed by
compression sleeve.
9. Insert tube into valve fully and tighten nut.
10. Turn on water supply and check for leaks.

*CODE VALVE IS INCLUDED WITH AUTOMATIC MODELS ONLY