Condensate piping – John Wood Condensing - JWC111-SV Manuel d'utilisation

Page 21

Advertising
background image

21

• This water heater is a high efficiency, fully condensing appliance which produces condensate dur-

ing operation. The water heater heater incorporates a collection, neutralization, and removal system

which must be properly drained in order to ensure proper operation of this appliance.

• The water heater is supplied with a pre-installed condensate neutralization system. No additional

neutralizer is required unless local code dictates otherwise.

• In order to drain the condensate, a 1/2" threaded fitting is provided at the base of the water heater.

Do not reduce the size of this fitting or the drain piping to less than 1/2".

• Use plastic pipe, such as PVC, for the drain line. Do not use steel, black iron, or any other material

which can corrode when placed into contact with water.

• Keep the length of the drain pipe as short as possible. Long runs or applications where the nearest

drain is above the water heater will require the use of a condensate pump. Size the pump to allow for

a maximum condensate discharge of 2 GPH from the water heater.

• Horizontal runs must be sloped 1/4" per foot towards the drain or condensate pump.
• The end of the drain pipe must not be submerged in water or blocked in any way.
• Be sure to check that condensate is freely flowing from the drain piping after the system has been

installed. Condensate will begin flowing out of the water heater within 15 minutes after operation has

started.

• Take measures to prevent the condensate drain lines from freezing (insulation, heat tape, electric

heaters, etc.).

11.

Condensate Piping

Slope pipe downwards
1/4" per foot.

1/2" PVC pipe

The end of the drain pipe
must have an air gap.

The end of the drain pipe
must have an air gap.

Condensate piping to floor drain

Floor drain

Slope pipe downwards
1/4" per foot.

1/2" PVC pipe

1/2" PVC elbow

3/8" ID tubing*

* Install tubing according to pump
manufacturer's instructions.

Condensate piping with pump

Condensate pump

KEEP CLEARANCE

DO NOT FIT
ANY VALVES

DO NOT FIT
ANY VALVES

Advertising