Power+™ Trip Units

Chapter 1. Introduction

1

1–1 Applications

The Power+™ Trip Units described in this publication are
used on WavePro™ low-voltage power circuit breakers.

Figure 1 shows the Power+ Trip Unit.

Figure 1. Front view of the Power+ Trip Unit.

1–2 General

Power+ Trip Units are the same size and have the same 50-
pin male D-sub connector as the RMS9D series of
MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip
Units.

Power+ Trip Units may be tested with the Trip Unit
installed in the circuit breaker, the rating plug installed in
the Trip Unit, and the breaker carrying current. The Test
Kit plugs into the test socket of the rating plug. The Test
Kit catalog number is TVRMS2 and its operation is
described in GEK–97367.

Power+ Trip Units are removable from the circuit breaker.
For instructions on installing and removing the Trip Unit,
see Chapter 4.

CAUTION: Removal of a Trip Unit from its breaker must
be performed with the breaker in the

OPEN

or

TRIPPED

position. Draw-out breakers should be racked out first.

ATTENTION: Pour retirer déclencheur, le disjoncteur
doit être en position ouverte ou déclenchée. Les
disjoncteurs débrochables doivent ètre en position
débrochée.

CAUTION: Do not attempt to operate the breaker without
its assigned Trip Unit. Installation of an incorrect Trip
Unit may result in unsafe operation of the breaker.

ATTENTION: Ne pas utiliser le disjoncteur sans son
déclencheur. Une mauvaise installation du déclencheur
peut être dangereuse.

NOTE: Trip Units as received may have settings that are
undesirable for the specific application. Ensure that
settings are appropriately adjusted before energizing.

NOTE: Les disjoncteurs sont livrés avec des réglages
standards qui peuvent être inadéquates pour certaines
applications. Vérifier ces réglages avant de mettre le
disjoncteur sous tension.

1–3 Trip Unit Functions

Power+ Trip Units have specific standard and optional
functions, with the current rating determined by
installation of the appropriate interchangeable rating
plug. The standard functions of the Trip Unit are as
follows:

• Overcurrent protection

– Long-time protection
– Instantaneous protection

The optional functions available are as follows:

• Protection

– Short-time protection, with or without I

2

T

– Ground-fault protection, with or without I

2

T

• Status

– Trip targets (with or without ground-fault trip

indication)

– Health monitor