Power+™ trip units chapter 1. introduction, 1–6 equipment interfaces, 1–7 trip unit information – GE Industrial Solutions WavePro Manuel d'utilisation

Page 10

Advertising
background image

Power+™ Trip Units
Chapter 1. Introduction

4

1–6 Equipment Interfaces

Power+ Trip Units do not usually require connections
within the equipment, since all wiring is contained within
the circuit breaker. The only connection is for the neutral
sensor, which uses a special dedicated disconnect.

CAUTION: Neutral current sensors are required for
single-phase, three-wire and three-phase, four-wire
systems. When the Trip Unit is connected to a three-
phase, three-wire system, the neutral sensor terminals of
the breaker are left open. Do not short any neutral
current sensor terminals in a three-phase, three-wire
system, as this could result in damage to, or malfunction
of, the electrical system.

ATTENTION: Un transformateur de courant de neutre est
nécessaire pour les réseaux 3 phases + neutre. Si le neutre
n’est pas distribué, les bornes de neutre du déclencheur
doivent être laissées ouvertes. Ne pas les court-circuiter
(ceci peut endommager le déclencheur et entrainer un
mauvais fonctionnement du système électrique.

1–7 Trip Unit Information

Trip Unit Label Information

Following are descriptions of the various numbers on the
front of the Trip Unit, as shown in Figure 1.

Top center – Serial number of the breaker in which the

Trip Unit is installed, such as

01234567891

.

Top-left corner – Serial number of the Trip Unit, such

as

RMS71234567

.

Top-right corner – Date of manufacture code, such as

P1121=

.

Right center above rating plug – Catalog number of the

Trip Unit, such as

J220LSIT1

.

Right center, below catalog number – Current sensor

rating in amperes.

There are two more labels on the Trip Unit that are not
generally visible when it is plugged into a breaker.

Side of unit – Bar code giving the catalog number of

the Trip Unit.

Rear of unit – Yellow caution label.

Selector Switches

The following selector switches are present on the front of
the Trip Unit. See Chapter 2, Setup Mode, for a complete
description of each function.

• Long-time pickup
• Long-time delay
• Short-time pickup (optional)
• Short-time delay (optional)
• Instantaneous pickup
• Ground-fault pickup (optional, on rating plug)
• Ground-fault delay (optional, on rating plug)

Advertising