Napoleon Fireplaces XIR4 Manuel d'utilisation

Page 9

Advertising
background image

W415-1194 / A / 12.19.13

9

EN

While the liners must be continuous from the appliance to the chimney cap, to

achieve the needed length, they may be coupled, using an approved coupler

and sealant.

We recommend that exhaust vents that pass through unheated spaces,

such as tall exterior chimneys, be wrapped in a protective sleeve to minimize

condensation and reverse fl ow symptoms. See Trouble Shooting for details.

This appliance is approved for use with a 3" (76mm) exhaust and air intake.

A. OUTSIDE: Slip the one end of a liner a minimum of 2" (51mm) over

the sleeve of the air terminal. Secure using 3 screws. Then seal the

joint and screw heads with high temperature sealant. Repeat with the other liner.

NOTE: We recommend that the other end of the exhaust liner be marked to eliminate the

exhaust liner being connected to the intake collar at the appliance.

B.

Gently stretch the liners to the

required lengths and insert into

the chimney. Trim and fi t the

fl ashing plate to suit the chimney

termination. Place the air terminal

onto the top of the chimney.

Make weather tight by sealing

with caulking (not supplied).

Fasten to the chimney with

screws and plugs (not supplied).

C. INSIDE: Remove the securing

screw from the front of the vent

mounting plate. Pull the vent

mounting plate only, back into

the track, to the front stop. Start

the slider back into position. Re-

secure the screw. The appliance

may now be pushed into its

fi nal position inside the wood

burning appliance, and the screw

tightened until the slider has

been pulled tight to the front stop.

D.

Route the fl ex liners through

the slider. Attach and secure

the liners to the vent mounting plate using the same procedure as before, ensuring that the marked

exhaust liner is attached to the exhaust collar.

FLASHING
PLATE

2” (50.8mm)
OVERLAP

MILL-PAC

INTAKE

EXHAUST

SECURING

SCREW

SLIDER

MOUNTING

PLATE

HIGH TEMP

SEALANT

2” (50.8mm)

OVERLAP

3” (76.2mm)

LINERS

EXHAUST

INTAKE

VENT MOUNT

ASSEMBLY

3.2 CHIMNEY

CONNECTION

Chimney installation must conform to both national and local code requirements. The chimney must be lined
with one 3" (76mm) diameter liner for intake and one 3" (76mm) diameter liner for exhaust. The minimum and
maximum vent lengths are 10 feet (3m) and 35 feet (11m) respectively.
Recommended kits come in 3 lengths:

2-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST:

GDI-320KT VENT KIT 20FT (6m)

GDI-325KT VENT KIT 25 FT (7m)

GDI-335KT VENT KIT 35 FT (11m)

Advertising