Warning, 0 adjustments – Napoleon Fireplaces Castlemore GDS26 Manuel d'utilisation

Page 38

Advertising
background image

38

W415-0827 / D / 08.10.12

9.0 ADJUSTMENTS

9.1 PILOT INJECTOR AND ORIFICE REPLACEMENT

BURNER
ASSEMBLY

ORIFICE

LOCATION

A.

Turn off the electrical and gas supply to the appliance.

B.

Remove the cast front, glass viewing door and log set.

C.

Remove the 2 securing screws. Slide the burner assembly to the right and lift out.

D.

Using a deep socket wrench, remove the main burner orifi ce. A back-up wrench
must be used on the manifold, located below the housing to ensure that the
aluminum tubing does not twist or kink. Replace the correct burner
orifi ce using pipe thread compound.

E.

Loosen nut and replace with appropriate injector

F.

Reinstall the burner ensuring that the Venturi tube fi ts over the orifi ce.
NOTE: Check and adjust, if necessary, the primary air to 3/8” for
propane and 3/16” for natural gas. Replace the screws.

G.

Turn on the gas supply and check for gas leaks by brushing on a
soap and water solution.

DO NOT USE OPEN FLAME.

H.

Replace the log set. Then light the pilot and main burner to ensure
that the gas lines have been purged.

I.

Replace the glass viewing door and cast front. Turn on the electrical supply to the
appliance.

Purge all gas lines with the glass door removed. Assure that a continuous fl ow is at the
burner before re-installing the door.

!

WARNING

9.2 PRESSURE

CHECK

Check Pressure Readings:

Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3
turns and then placing pressure gauge tubing over the test point. Gauge should
read 7” (minimum 4.5”) water column for natural gas or 13” (11” minimum) water
column for propane. Check with main burner operating on “HI”.

Outlet pressure can be checked the same as above using screw (B). Gauge
should read 3.5” water column for natural gas or 10” water column for propane.
Check with main burner operating on “HI”.

AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL.
DO NOT OVERTORQUE.

Leak test with a soap and water solution.

39.5

A

B

THIS INSTALLATION SHOULD BE DONE BY A QUALIFIED INSTALLER AND SHALL BE IN

COMPLIANCE WITH LOCAL CODES. IN THE ABSENCE OF LOCAL CODES, USE THE CURRENT

CAN1-B149 INSTALLATION CODE IN CANADA, OR THE CURRENT NATIONAL FUEL GAS CODE ANSI

Z223.1 IN THE UNITED STATES.

Advertising