Back wall side w a ll back wall side w a ll – Napoleon Fireplaces Castlemore GDS26 Manuel d'utilisation

Page 30

Advertising
background image

30

W415-0827 / D / 08.10.12

* HORIZONTAL VENT SECTIONS:

A minimum clearance of 1" at the bottom and sides and 2" at the top of the vent pipe in all horizontal runs to

combustibles is required. Use fi restop spacer W010-1313 and shield W585-0240 (supplied).

* VERTICAL VENT SECTIONS:

A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required. Use fi restop spacer

W010-1313 (supplied).

** For top vent vertical termination, see "REAR EXIT" for specifi c clearances.

At a distance of 2" from the wall, installation or service to the blower may not be practical. A minimum of 5" will

be required in order to install or service the blower.

Minimum clearance to combustible construction from appliance and vent surfaces:

A

- 2"

B

-

5"

C

- 2"

Combustible Framing:

-

1" to bottom and sides of the vent pipe*

-

2" to top of the vent pipe*

NOTE: Appliance should not be installed directly on

carpeting.

Rear Exit:

-

47 1/2" to ceiling from base of the appliance

Top Exit:

-

51" to ceiling from base of the appliance**

BACK WALL SIDE W

A

LL

BACK WALL SIDE W

A

LL

1”

2”

47 1/2”

35 1/2”

5”

BRICK

COMBUSTIBLE

NON-COMBUSTIBLE

29 1/8”

MINIMUM

PLUS RISE *

0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK AND
STONE.

12”

MANTEL, SHELF,

OR CEILING

The appliance requires a minimum ceiling height of 47 1/2" for a rear vent. For temperature requirements, the
space around and above the appliance must be left unobstructed.

REAR EXIT

4.4 MINIMUM CLEARANCE TO COMBUSTIBLES

Advertising