7 elbow vent length values, 8 top exit horizontal termination – Napoleon Fireplaces Castlemore GDS26 Manuel d'utilisation

Page 14

Advertising
background image

14

W415-0827 / D / 08.10.12

3.7 ELBOW VENT LENGTH VALUES

15.1

FEET

INCHES

1° 0.03

0.5

15° 0.45 6.0
30° 0.9 11.0
45° 1.35 16.0
90°*

2.7

32.0

* The fi rst 90° offset has a zero value and is shown in the formula as - 90°

3.8 TOP EXIT HORIZONTAL TERMINATION

16.1A

Simple venting confi guration (only one 90° elbow)

(H

T

) < (V

T

)

For vent confi gurations requiring more than one 90° elbow, the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Example:
V

1

= 3 FT

V

2

= 8 FT

V

T

= V

1

+ V

2

= 3 FT + 8 FT = 11 FT

H

1

= 2.5 FT

H

2

= 2 FT

H

R

= H

1

+ H

2

= 2.5 + 2 = 4.5 FT

H

O

= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT

H

T

= H

R

+ H

O

= 4.5 + 5.4 = 9.9 FT

H

T

+ V

T

= 9.9 + 11 = 20.9 FT

Formula 1:

H

T

< V

T

9.9 < 11

Formula 2:

H

T

+ V

T

< 40 FT

20.9

<

40

Since both formulas are met, this vent confi guration is acceptable.

See graph to determine the required vertical

rise V

T

for the required horizontal run H

T

.

The shaded area within the lines represents

acceptable values for H

T

and V

T

0

2.5

5

7.5

10

12.5

15

40

10

20

30

17.5

20

39

REQUIRED

VERTICAL

RISE IN

FEET V

T

HORIZONTAL VENT RUN PLUS OFFSET IN

FEET H

T

90°

90°

90°

V

1

V

2

H

1

H

2

Advertising