Warning – Napoleon Fireplaces Swarovski - LHD50SS Manuel d'utilisation

Page 30

Advertising
background image

30

W415-0839 / D / 08.15.12

* Within the appliance enclosure a 6” clearance between the top of the vent pipe and combustible materials is
required. All other clearances within the enclosure, including where the vent pipe exits the enclosure are sub-
ject to 2” to the sides and bottom and 3” to the top for horizontal and 1” for vertical.
** See venting section.

IMPORTANT:

The LHD50SS requires a minimum inside enclosure height of 60”, measured from the bottom of

the appliance. For temperature requirements, this area must be left unobstructed. It is recommended that the
enclosure be ventilated at the top and bottom to circulate the hot air.

Before fi nishing in the appliance test the operation using the remote control, cycling it through all of its different

modes, see “OPERATION” section. Check pressure readings, see “PILOT BURNER ADJUSTMENT” section.

Once fi nished in, access to the control components can only be done through the inside of the appliance.

5.3 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES

!

WARNING

THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THESE MATERIALS NEVER OVERHANG

INTO THE APPLIANCE OPENING.

STEEL STUD
FRAME

TOP OF ENCLOSURE

6”*

0” IF NON-
COMBUSTIBLE
FINISHING IS
USED SUCH AS
BRICK AND
STONE.

3”

2”

COMBUSTIBLE

NON-COMBUSTIBLE

60”

MINIMUM

ENCLOSURE

HEIGHT

TOP OF
APPLIANCE
OPENING

28”

MINIMUM

32”

MINIMUM

COMBUSTIBLE

MATERIAL

51”

MINIMUM

PLUS

RISE**

NON-COMBUSTIBLE

NOTE: JOINT COMPOUNDS AND TAPES
THAT ARE RESILIENT TO HEAT AND
CRACKING SHOULD BE USED WHEN
TAPING AND MUDDING SEAMS.

9” TO

SIDEWALL