Warning, 0 venting – Napoleon Fireplaces Swarovski - LHD50SS Manuel d'utilisation

Page 10

Advertising
background image

10

W415-0839 / D / 08.15.12

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab

venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and

air terminal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-

Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided

with the venting components.

A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:

For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the installation
procedure found on the website for your venting supplier.

For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using a

red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent

pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance fl ue collar

which must be sealed using the black high temperature sealant Mill Pac.

PART

5”/8”

SUPPLIER

WEBSITE

Duravent

W175-0170

Wolf Steel

www.duravent.com

Amerivent

5DSC-N2

American Metal

www.americanmetalproducts.com

Direct Temp

5DT-AA

Selkirk

www.selkirkcorp.com

SuperSeal

5DDA

Metal-Fab

www.mtlfab.com

3.0 VENTING

3.1 VENTING LENGTHS AND COMPONENTS FOR DIRECT VENT INSTALLATIONS

7.2B

THIS APPLIANCE USES A 5” EXHAUST / 8” AIR INTAKE VENT PIPE SYSTEM.

Refer to the section applicable to your installation.

For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.

NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.

NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.

!

WARNING

RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.

IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3 FEET

FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT

NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM

COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT

NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES

FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT

PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS

REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF

EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.