Simple venting configurations.

See graph to determine the required vertical rise V

T

for the

required horizontal run H

T

.

REQUIRED

VERTICAL

RISE IN FEET

(METERS) V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H

T

For vent configurations requiring more than two 90° elbows the following formulas apply:

Formula 1: H

T

< 3V

T

Formula 2: H

T

+ V

T

< 40 feet (12.2m)

Example:
V

1

= 2 FT (0.6m)

V

2

= 1 FT (0.3m)

V

3

= 1.5 FT (0.5m)

V

T

= V

1

+V

2

+V

3

= 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5FT (1.4m)

H

1

= 6 FT (1.8m)

H

2

= 2 FT (0.6m)

H

R

= H

1

+ H

2

= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)

H

O

= .03 (four 90° elbows - 90°)

= .03 (360° - 90°) = 8.1 FT (2.5m)
H

T

= H

R

+ H

O

= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)

H

T

+ V

T

= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6 FT (6.3m)

Formula 1:

H

T

< 3V

T

3V

T

= 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)

16.1FT (4.9m) > 13.5FT (4.1m)

Since this formula is not met, this vent configuration is unacceptable.
Formula 2:

H

T

+ V

T

< 40 feet (12.2m)

20.6FT (6.3m) < 40 (12.2m)

Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will
need to be established to satisfy both formulas.

The shaded area within the lines represents acceptable

values for H

T

and V

T

0

5

(1.5)

10

(3.1)

15

(4.6)

20

(6.1)

10 (3.1)

20 (6.1)

3 (0.9)

25

(7.6)

30

(9.1)

19 (5.8)

90°

V

1

V

2

H

1

H

2

90°

90°

90°

V

3

18.1_2B

NOTE: All vent parameters are stated for rigid venting. If using approved Wolf Steel Ltd. fl exible
venting then maximum horizontal requirements are reduced by 25%.

NOTE: There MUST be a 25% reduction in total horizontal length (H

T

) when using fl ex vent.