0 adjustments – Napoleon Fireplaces Tureen™ - GD82T-TE Manuel d'utilisation

Page 41

Advertising
background image

41

W415-0769 / A / 12.10.10

Adjust the pilot screw to provide properly sized fl ame. Turn in a clockwise
direction to reduce the gas fl ow.

Inlet pressure can be checked by turning screw (A) counter-
clockwise until loosened and then placing pressure gauge
tubing over the test point. Gauge should read 7” (minimum 4.5”)
water column for natural gas or 13” (11” minimum) water column for
propane. Check that main burner is operating on “HI”.

Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5” water column for natural gas or 10” water column
for propane. Check that main burner is operating on “HI”.

AFTER TAKING PRESSURE READINGS, TIGHTEN SCREWS FIRMLY TO
SEAL. DO NOT OVER TORQUE. LEAK TEST.

39.2

A

B

PILOT

BURNER

THERMOCOUPLE

THERMOPILE

10.0 ADJUSTMENTS

FLUE COLLAR

RESTRICTOR PLATE

TOP OF FIREBOX

Vertical terminations may display a very active fl ame. If this
appearance is not desirable, the vent exit must be restricted
using restrictor plate W500-0205. This reduces the velocity
of the exhaust gases, slowing down the fl ame pattern and
creating a more traditional appearance.

The plate has a series of holes to allow for adjustment.
Remove the two screws on either side of the exhaust col-
lar inside the fi rebox. Install the plate in the desired set of
holes, then replace the screws.

It is recommended to secure in the third set of holes which
causes the greatest amount of restriction for vent lengths
between 15 and 30 feet.

10.1 RESTRICTING VERTICAL VENTS

10.2 PILOT BURNER ADJUSTMENT