Warning – Napoleon Fireplaces Tureen™ - GD82T-TE Manuel d'utilisation

Page 10

Advertising
background image

10

W415-0769 / A / 12.10.10

45.6

10” MINIMUM

24” MAXIMUM

56”

PLUS

RISE

46”

46”

16” MINIMUM

3 FEET

MINIMUM

40 FEET

MAXIMUM

When venting, the horizontal run must be kept to a maximum of 20 feet. If a 20 foot horizontal run is required,
the appliance must have a minimum vertical rise immediately off the appliance of 57”. When terminating verti-
cally, the vertical rise is a minimum 3 feet and a maximum 40 feet above the appliance.

* FIRST TWO

FEET

REQUIRES

INSULATION

SLEEVE

!

WARNING

THE FIRST 2 FEET OF OUTER 7 “ DIAMETER VENT PIPE FROM THE APPLIANCE MUST BE WRAPPED

IN THE 1” THICK INSULATION SLEEVE (SUPPLIED). MAKE SURE THE INSULATION IS PULLED DOWN

TIGHT TO THE APPLIANCE WHEN INSTALLED. THERE AFTER, A 2” CLEARANCE ALL AROUND THE

VENT PIPE FROM COMBUSTIBLE MATERIALS ON ALL HORIZONTAL VENT SECTIONS IS REQUIRED.

3.2 TYPICAL VENT INSTALLATION