Napoleon Fireplaces Torch - GT8 Manuel d'utilisation

Page 20

Advertising
background image

20

W415-0794 / D / 05.30.11

Minimum clearance to combustible construction from appliance and vent surfaces:
Appliance framing:

- 6” to top

-

0”

to

stand-offs

(Rear

and

sides)

Vent pipe*:

- 2” top

- 1” sides and bottom

Recessed depth:

-

7”

WITHOUT

FRAME INSTALLED

WITH FRAME INSTALLED

5.1 MINIMUM CLEARANCE TO COMBUSTIBLES

2” MIN.*

12” MIN. TO

COMBUSTIBLES

(to ceiling or mantle)

1 1/2” MIN.

* Any protruding

finishing material

installed in this space

(ie. baseboards) must

leave 2” of

unobstructed clearance

to allow for full rotation

of the control door.

COMBUSTIBLE NON-COMBUSTIBLE

2”

1”

0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK AND
STONE.

BRICK

6” MIN.

FRAME

CONTROL

DOOR (OPEN

POSITION)

* HORIZONTAL VENT SECTIONS:

A minimum clearance of 1” at the bottom and sides and 2” at the top of the

vent pipe in all horizontal runs to combustibles is required. Use fi restop spacer W010-1961 (supplied).

* VERTICAL VENT SECTIONS:

A minimum of 1” all around the vent pipe on all vertical runs to combustibles

is required. Use fi restop spacer W500-0358 (not supplied).