4 horizontal termination – Napoleon Fireplaces Torch - GT8 Manuel d'utilisation

Page 11

Advertising
background image

11

W415-0794 / D / 05.30.11

3.4 HORIZONTAL

TERMINATION

MIN

MAX

Allowable 3” vent connections (excluding appliance and air terminal connections)

N/A

1

Rise per foot (recommended)

1/4”

N/A

Rise per foot (allowable)

0”

N/A

Horizontal run (If vent run does not include vertical rise)

4”

24”

Horizontal run (if vent run includes vertical rise)

4”

7 FT

Vertical run
(* Immediately off the appliance, if 7 FT maximum horizontal run is required)

18”*

7 FT

0

1 2 3 4 5 6 7 8 9 10

10

9

8

7

6

5

4

3

2

1

1.5

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (

H

T

)

REQUIRED
VERTICAL
RISE IN
FEET (

V

T

)

See graph to determine the required vertical rise

V

T

for the required horizontal rise

H

T

.

4” MIN.

24” MAX.

8”

18” MINIMUM

MAXIMUM

HORIZONTAL

7 FT MAX.

4”

MIN.

8”

4”

MIN.

9 FT

MAX.

MAXIMUM

VERITICAL