Step 2: cabinet preparation, Caution – Thermador PD304 Manuel d'utilisation

Page 7

Advertising
background image

4

Step 2: Cabinet Preparation

1. The range is a free standing unit. If the unit is to be

placed adjacent to cabinets, the clearances shown
in Fig. 1 are required. The same clearances apply
to island installations, except for the overhead
cabinets, which must have a space wide enough
to accept the flared island hood, as indicated in
Fig. 1.

2. The 36" ranges may be recessed into the cabi-

nets beyond the edge of the front face of the oven
(See Figures 2A and 2B). The 30" and 48" ranges
are not approved to be installed flush with the
cabinets.

CAUTION

In these installations, the door and cabinet on
36-inch models can cause a pinching hazard.

NOTE: The maximum depth of over head cabinets
installed on either side of the hood is 13".

A 36-inch minimum clearance is required between
the top of the range and the bottom of an unprotected
cabinet. A 30-inch minimum distance is necessary
when the bottom of the wood or metal cabinet is
protected by not less than 1/4 inch of a flame
retardant material covered with not less than No. 28
MSG sheet steel, 0.015 inch (0.4 mm) thick stainless
steel, 0.024 inch (0.6 mm) aluminum, or 0.020 inch
(0.5 mm) thick copper. Flame retardant materials
bear the mark:

UNDERWRITERS LABORATORIES INC.
CLASSIFIED MINERAL AND FIBER BOARDS
SURFACE BURNING CHARACTERISTICS
Followed by the flame spread and smoke ratings.
These designations are shown as “FHC (FIame
Spread/Smoke Developed).” Materials with “O”
flame spread ratings are flame retardant. Local codes
may allow other flame spread ratings.

3. The gas and electrical supply should be within the

zones shown in Fig. 3A.

4. Any openings in the wall behind the range and in

the floor under the range must be sealed.

5. When there is less than a 12" horizontal clear-

ance between combustible material and the
back edge of the range above the cooking sur-
face, a Thermador Low Back or High Shelf
backguard must be installed. (See Fig. 2A). When
clearance to combustible material is over 12",
a Thermador Island Trim may be used. (See Fig.
2B). Figures 2A and 2B indicate the space
required for each type of backguard.

6. Always keep appliance area clear and free from

combustible materials, gasoline and other flam-
mable vapors and liquids.

7. Do not obstruct the flow of combustion and

ventilation air to the unit.

Advertising