Vent pipe system, Venting, Condensate drain line – Polaris PC 175-50 3NV Manuel d'utilisation

Page 6

Advertising
background image

6

Condensate Drain Line

All parts of the condensate trap are glued except for the

1/2” CPVC drain stem joint at the elbow (see figure 3A).

This assembly can be turned with the outlet of the tee

oriented as needed.
Once orientation direction is decided, remove the unglued

joint from the elbow at the bottom and apply a suitable

cement to joint. Re-insert the joint fully and quickly into

the elbow making sure to orient it before the cement sets.

Connect the remaining piping and run the condensate drain

line to a suitable drain.
Important: Be sure the drain stem joint is inserted against

the stop in the elbow. Failure to do so may result in

improper water heater operation.
If required by local codes, install a condensate neutralizer

cartridge on the drain line (see figure 3B).
The condensate drain line must be routed to a suitable

drain. If no floor drain is available or the drain is above

the level of the condensate line, install a condensate pump

that is resistant to the acidic condensate. These pumps are

available from local distributors. If the pump is not resistant

to acidic water, a condensate neutralizer must be used

ahead of the pump.
When installing the drain line, note the following:

Plastic pipe or tubing must be used to connect the

condensate drain to a suitable drain or condensate

pump. Do not use copper tubing, iron, or steel pipe for

the condensate drain line.

Condensate drain lines should be installed in condi-

tioned areas only. Drain lines installed in areas that are

subject to freezing temperatures should be wrapped

with a nationally recognized/listed heat tape and/or

approved insulation for freeze protection. Install per

manufacturer’s instructions.

Do not common drain with the temperature and pres-

sure relief valve or the condensate line from an air

conditioner evaporator coil.

Slope the condensate drain toward the inside floor

drain or condensate pump.

The condensate drain line and connection to the drain

piping must comply with all local codes.

Do not run the condensate line into the metal drain
pan.

VENT PIPE SYSTEM

Carbon Monoxide Hazard

Follow all instructions to locate and install

the vent pipe system.
Instructions can be found in this manual, in

state or local codes (or the authority having

jurisdiction), or in the absence of such, the

National Fuel Gas Code, ANSI Z223.1, NFPA

54, Current Edition. Canadian installations

must be performed in accordance with

CAN/CSA-B149.1, Current Edition.
Failure to properly locate and install the

vent pipe system can result in death or

carbon monoxide poisoning.

Venting

This water heater has a direct vent system in which all air

for combustion is taken from the outside atmosphere and

all combustion products are discharged to the outdoors.

This water heater must be properly vented for removal

of exhaust gases to the outside atmosphere. Correct

installation of the vent pipe system is mandatory for the

safe and efficient operation of this water heater and is an

important factor in the life of the unit.

Vent pipe installation must be performed in accordance

with state and local codes, or in the absence of such, the

National Fuel Gas Code, NFPA 54, ANSI Z223.1-current

edition. Canadian installations must be performed in

accordance with CAN/CSA-B149.1-current edition.
When replacing an existing Polaris

®

unit, it is recommended

that the venting system be reviewed for compliance with

the requirements contained in this installation manual. If the

venting is not in compliance, it is recommended that the

appropriate changes be made to bring it into compliance.

Note: It is important that the factory-installed air inlet

filter be inspected at least twice each year and cleaned if

necessary. See “Integrated Filter Installation, Preventive

Maintenance”. Note: if the vent system is not in compliance

with the current installation manual, the manufacturer

reserves the right to evaluate the installation prior to

granting any warranty on service claims.
Important: Check to make sure the vent pipe is not

blocked in any way.
Note: Do not common vent this water heater with any

other appliance. Do not install in the same chase or

chimney with a metal or high-temperature plastic from

another gas or fuel burning appliance.

Figure 3B: Condensate Drain

Advertising
Ce manuel est liée aux produits suivants: