Gas Pressure Testing

Important: This water heater and its gas connection must

be leak tested before placing the appliance in operation.

If the code requires the gas lines to be tested at a

pressure of 14” W.C. (3.486 kPa) or greater, the water

heater and its manual shut-off valve must be discon-

nected from the gas supply piping system and the line

capped.

If the gas lines are to be tested at a pressure less

than 14” W.C. (3.486 kPa), the water heater must be

isolated from the gas supply piping system by closing

its manual shut-off valve.

Nationally listed/recognized fuel gas and carbon

monoxide(CO) detectors are recommended in

all applications and should be installed using the

manufacturer’s instructions and local codes, rules, or

regulations.
Note: Air may be present in the gas lines and could prevent

the burner from lighting on initial start-up. The gas lines

should be purged of air by a qualified service technician

after installation of the gas piping system.

Explosion Hazard

Have a qualified person make sure that

the L.P. gas operating pressure does not

exceed 13” water column (3.237 kPa).

Examples of a qualified person include

licensed heating personnel, authorized

gas company personnel, and authorized

service personnel.

Failure to do so can result in death,

explosion, or fire.