Vertical terminations, Venting additional polaris, Units – Polaris PC 175-50 3NV Manuel d'utilisation

Page 11: Figure 9: vertical termination, Figure 9a, 9b figure 9c, 9d

Advertising
background image

11

VERTICAL TERMINATIONS

When 3 inch pipe is used between the water heater and the

roof, reduce it to 2 inch pipe before penetrating the roof.

A maximum of 18 inches (45.7 cm) of 2 inch pipe may be

used between the 3 inch transition and the inside of the

roof.
The vertical inlet air termination requires a return bend

or two short or long sweep radius 90 elbows to keep the

inlet downward and prevent entry of rain. These elbows

are considered part of the termination and should not be

included when calculating the maximum allowable vent

pipe length. Refer to figure 9 for the proper location of the

air inlet with respect to the exhaust outlet termination. The

vertical exhaust outlet termination is a 2 inch (30.5 cm) pipe

which terminates at least 12 inches (30.5 cm) above the

inlet air termination.
The air inlet and exhaust outlet terminations must be at

least 12 inches (30.5 cm) above the roof line or anticipated

snow levels. See figure 9 below.
Note: See “Venting Additional Polaris

®

Units” below if

installing more than one Polaris

®

gas water heater.

Venting Additional Polaris

®

Units

When using two (2) Polaris

®

units, install vent terminations

using either Method A or Method B below:

When using three or more Polaris

®

units, install vent

terminations per Method C or Method D:

Figure 9: Vertical Termination

Notes:
1. Support Horizontal Pipe Every

Four Feet (1.2 m). Support Vertical

Pipe Every Six Feet (1.8 m).

2. When Using 3 Inch Pipe, Reduce To

2 Inches Before Penetrating The

Roof.

3. 18 Inch (45.7 cm) Maximum When

Using 2 Inch Pipe.

4. Increase The 12 Inch (30.5 cm)

Minimum Above Grade To Keep

Terminal Openings Above Anticipated

Snow Levels.

4” (10 cm) Max.

12” (30.5cm) Min.

Above Roof or

Anticipated Snow

Level. See Note 4.

12” (30.5 cm) Min.

12” (30.5 cm)

Min.

4” (10 cm)

Max.

12”

(30.5 cm)

Min.

*

*

3” (7.6cm) Max.

4” (10cm)

Max.

3”

(7.6 cm)

Max.

4”

(10cm)

Max.

36” (91.4 cm)

Minimum

3” (7.6 cm) Max.

4”

(10cm)

Max.

3”

(7.6 cm)

Max.

4”

(10cm)

Max.

4”

(10cm)

Max.

36” (91.4 cm)

Minimum

4”

(10cm)

Max.

4”

(10cm)

Max.

4”

(10cm)

Max.

36” (91.4 cm)

Minimum

36” (91.4 cm)

Minimum

Figure 9A, 9B

Figure 9C, 9D

Advertising
Ce manuel est liée aux produits suivants: