Do not use with piping that has been treated with

chromates, boiler seal or other chemicals and do not

add any chemicals to the water heater piping.

If the space heating system requires water temperatures

in excess of 120°F (48.9°C), a mixing valve (provided)

must be installed per the manufacturer’s instructions

in the potable hot water supply to limit the risk of scald

injury.

Pumps, valves, piping and fittings must be compatible

with potable water.

A properly installed flow control valve is required to pre-

vent thermosiphoning. Thermosiphoning is the result

of a continuous flow of water through the air handler

circuit during the off cycle. Weeping (blow off) of the

temperature and pressure relief valve (T & P) or higher

than normal water temperatures are the first signs of

thermosiphoning.

The hot water line from the water heater should be ver-

tical past any mixing valve or supply line to the heating

system to remove air bubbles from the system.

Do not connect the water heater to any system or

components previously used with non-potable water

heating appliances when used to supply potable water.

Storage Tank Installation

When installing the Polaris® with a storage tank, see figure

18 for piping suggestions.

Solar Installation

If this water heater is used as a solar storage heater or as
a backup for the solar system, the water supply tempera-
tures to the water heater tank may be in excess of 120°F
(48.9°C). A mixing valve must be installed in the water sup-
ply line to limit the supply temperature to 120°F (48.9°C).
Note: Solar water heating systems can often supply water
with temperatures exceeding 180°F (82.2°C) and may
result in water heater malfunction.

Figure 17: Air Handler Piping Installation

Mixing Valve

Metal Drain Pan

6” (15.2cm)

Air Gap Max.

Adequate Drain