UPS SYSTEM INSTALLATION

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

4−20

NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For proper
operation the following must be true:

1A = 2A = 3A = 4A
1B = 2B = 3B = 4B

NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference
between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%.

Bypass Input to UPS Units

UPS 1

Battery

UPS 2

UPS 3

UPS 4

Output from UPS Units

Battery

Battery

Battery

1A

2A

3A

4A

1B

2B

3B

4B

Figure 4-17. Distributed Bypass Wire Length