2 ups output, 3 ups environmental – Powerware 9395 UPS 10001100 kVA Manuel d'utilisation

Page 170

Advertising
background image

PRODUCT SPECIFICATIONS

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

10−2

10.2.2

UPS Output

UPS Output Capacity

100% rated current

Output Voltage Regulation

"1% (10% to 100% load)

Output Voltage Adjustment
(Nominal +/–3%)

480 Vac nominal, adjustable from 466 Vac to 494 Vac

Output Voltage Harmonic Content

1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)

Output Current

See Table 3-4 on page 3−9 or Table 3-5 on page 3−10 for four UPM
models.

See Table 3-6 on page 3−11 or Table 3-7 on page 3−12 for three UPM
models.

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase
Displacement

3° for 100% maximum load imbalance (linear load)

Output Transients

"5% (10% to 100% load)

Frequency Regulation

"0.1 Hz free running

Synchronous to Bypass

+10% to −10%

"3%

Frequency Slew Rate

1 Hz per second maximum

Load Compatibility

0.9 pF Leading
0.8 pF Lagging

Overload Capability

110% for 10 minutes
125% for 30 seconds
150% for 10 seconds

10.2.3

UPS Environmental

Operating Temperature

0 to 40°C (32 to 104°F) without derating. The recommended
operating temperature is 25°C (77°F).

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

Storage Temperature

–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self-discharge)

Relative Humidity (operating and
storage)

5% to 95% maximum noncondensing

Acoustical Noise

76 dB at a 1m distance, A weighted

EMI Suppression

Meets FCC Regulation 47, Part 15, for class A devices

Electrostatic Discharge (ESD)
Immunity

Meets IEC 801-2 specifications. Withstands up to 25 kV pulse
without damage and with no disturbance or adverse effect to the
critical load.