4 electrically connecting the sections, From the hardware kit (see figure 4-7), Proceed to paragraph 4.4 – Powerware 9395 UPS 10001100 kVA Manuel d'utilisation

Page 52

Advertising
background image

UPS SYSTEM INSTALLATION

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

4−8

Front View Base Bracket

UPM Section Base

ISBM Section Base

Bracket from Kit

Screw from Kit

Screw from Kit

Top View Rear Bracket

UPM

Section Top

ISBM

Section Top

Screw from Kit

Screw from Kit

Bracket from Kit

Back

Top View Front Bracket

UPM

Section Top

Screw from Kit

Screw from Kit

ISBM

Section Top

Bracket from Kit

Front

Figure 4-7. ISBM Section to UPM Section Joining Brackets

4.4

Electrically Connecting the Sections

1.

Unfasten the front door latch and swing the door open (see Figure 4-1 on
page 4−2).

2.

Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.

3.

Remove the screws securing the ISBM section right bottom internal safety
shield panel and remove the panel to gain access to the internal input, output,
and battery terminals. Retain the hardware for later use.

NOTE AC and DC input intercabinet power wiring harnesses are supplied coiled and secured in the UPM
wireway on the left side of the UPM section (see Figure 4-6 on page 4−7).

4.

Locate the AC and DC input intercabinet power wiring harnesses (long cables
labeled xG1, xG2, and xG3). Remove wire ties as necessary and uncoil the
cables.

5.

Locate the 1G1, 1G2, 2G1, 2G2, 3G1, and 3G2 power wiring harnesses. Route
these harnesses through the wiring access in the right side panel of the ISBM
section to the AC Input to UPMs terminals. See Figure 4-8 on page 4−11 for
terminal locations.

Advertising