Powerware 9395 UPS 10001100 kVA Manuel d'utilisation

Page 133

Advertising
background image

UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

7−9

Table 7-4. Typical System Status Messages

Function

Message

UPS

Shutdown; Bypass; Online

Bypass

Off; On; Available

Maintenance Bypass

Off; On

Charger

Charger Off; Charging

UPM (during startup)

DC Starting, Charger Off; DC Starting, Close Battery
Breaker; Inverter Starting; Inverter Syncing; Ready; Online

UPM 1
UPM 2
UPM 3
UPM 4 (not displayed on three UPM model)

Offline; Shutdown, Charger Off; Ready; Ready, Charging;
Online, Charger Off; Online, Charging

Table 7-5. Command Menu Operation

Function

Subfunction

Operation

UPS Control Commands

Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.

Go to Normal

Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.

Go to Bypass

Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.

Load Off

Displays the Load Off screen (see paragraph 7.2.8).

Bypass Commands

Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.

Go to Bypass

Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.

Go to Normal

Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.

Load Off

Displays the Load Off screen (see paragraph 7.2.8).

Charger Control
Commands

Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command.

Charger On

Turns the battery charger on.

Charger Off

Turns the battery charger off

UPM Control
Commands

Use the up or down arrow pushbutton to highlight the command function desired, then press the
CONTROLS pushbutton to execute the command.

UPM On

Turns the UPM on without transferring the load to Normal mode. The Load is on bypass.

UPM Off

Transfers the load to bypass and turns the UPM off.

UPM Go to Normal

Turns the UPM on and transfers the load to Normal mode.

Charger On

Turns the battery charger on.

Charger Off

Turns the battery charger off

Advertising