UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

3−10

Table 3-5. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000, and 9395−1100/1100
– Separate Battery

Basic Unit Rating

Units

Rating 50/60 Hz

kVA

kW

1000

909

1100
1000

Input and Output Voltage

Volts

480/480

480/480

AC Input to UPS Rectifier (0.98 Minimum pF)

Full load current plus battery recharge current
(3) Phases, (1) Ground

A

Amps

1280

1500

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(5)

500

(5)

AC Input to UPS Bypass (Four Wire)

Full Load Current
(3) Phases, (1) Ground

B

Amps

1203

1323

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

500

(5)

AC Input to UPS Bypass (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

1203

1323

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(5)

500

(6)

DC Input from Each Battery Disconnect to Each UPS UPM

(1) Positive, (1) Negative

C

Amps per UPM

551

551

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

250

(3)

250

(3)

AC Output to Critical Load (Four Wire)

Full Load Current
(3) Phases, (1) Ground

D

Amps

1203

1323

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

500

(5)

AC Output to Critical Load (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

1203

1323

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(5)

500

(6)

Neutral Bonding Jumper (Four Wire Output Only)

Minimum Conductor Size
Number

AWG or kcmil

(each)

250

(1)

250

(1)

NOTE Callout letters

A

,

B

,

C

, and

D

map to Figure 6-6 on page 6−8.