UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

3−2

For Field Installed UPM (FI−UPM) weights and dimensions, refe to the Powerware
9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.8 on
page 1−7.

Table 3-1. UPS Cabinet Weights

Model

Section

Weight

kg (lb)

Shipping

Installed

Powerware 9395−1100/1000

ISBM

1850 (4078)

1750 (3858)

UPM

1590 (3505)

1482 (3267)

Powerware 9395−1100/1100

ISBM

1850 (4078)

1750 (3858)

UPM

1590 (3505)

1482 (3267)

The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Top of Cabinet

457.2 mm (18") minimum clearance for ventilation

From Front of Cabinet

914.4 mm (36") working space

From Back of Cabinet

None Required

From Right Side of Cabinet

152.4 mm (6") working space

From Left Side of Cabinet

None Required

The basic environmental requirements for operation of the UPS are:

S

Ambient Temperature Range:

0–40°C (32–104°F)

S

Recommended Operating Range: 20–25°C (68–77°F)

S

Maximum Relative Humidity:

95%, noncondensing

C

A

U

T

I

O

N

If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.

The UPS ventilation requirements are shown in Table 3-3.

Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation

Model

Rating

Input/Output

Voltage

Heat Rejection

BTU/hr

 1000 (kg−cal/hr)

Ventilation Required for Cooling Air Exhaust

Powerware 9395−1100/1000

1000 kVA

480/480

195 (49127)

Approximately 3020 liter/sec (6400 cfm)

Powerware 9395−1100/1100

1100 kVA

480/480

215 (54040)

Powerware 9395−1100/650

650 kVA

480/480

127 (31933)

Approximately 2265 liter/sec (4800 cfm)

Powerware 9395−1100/750

750 kVA

480/480

146 (36845)

Powerware 9395−1100/825

825 kVA

480/480

161 (40530)