Voltage at clock terminals – Honeywell Q682 Manuel d'utilisation

Page 23

Advertising
background image

23

69-0628B—1

AC voltage at
C-C terminals

Possible cause

check

Action

0 Vac.

1. System power Off.

1. Restore power.

2. Short in clock power supply wiring.

2. Replace wiring.

3. Limit switch contacts stuck open.

3. Free or replace limit switch.

4. Transformer supplying power is burned

out.

4. Replace transformer.

Up to 15 Vac.

1. System transformer used to power the

clock is inadequate.

1. Use additional (separate)

transformer.

2. Additional (separate) transformer used

to power the clock has inadequate
voltage.

2. Install transformer with proper

secondary voltage.

15 to 30 Vac.

1. Spring fingers on thermostat not

making proper contact with subbase
terminals.

1. Rebend spring fingers to a

45 degree angle to assure
proper contact.

2. Clock has failed.

2. Replace thermostat.

Voltage At Clock Terminals