SLC 500 BASIC and BASIC-T Modules 25

Publication 1746-IN009B-EN-P - August 2005

Operating Voltage and Current Requirement

Component

Operating Voltage

Current Requirement

Hand-Held Terminal

24V dc

0.105 A

Data Table Access Module

24V dc

0.104 A

Interface Converter

24V dc

0.060 A

IMPORTANT

The module receives its power from the SLC backplane. The
power consumption of the module must be taken into
consideration when planning your SLC 500 system. Refer to the
documentation supplied with your SLC 500 fixed or modular
controller for additional information on power supplies and
current requirements.

Communication

Maximum Distance Allowed in Meters (Feet)

Rate (bps)

RS-232

RS-423

RS-422

RS-485

300

15 (50)

1230 (4000)

1230 (4000)

1230 (4000)

600

15 (50)

920 (3000)

1230 (4000)

1230 (4000)

1200

15 (50)

770 (2500)

1230 (4000)

1230 (4000)

4800

15 (50)

245 (800)

1230 (4000)

1230 (4000)

9600

15 (50)

120 (400)

1230 (4000)

1230 (4000)

19200

15 (50)

60 (200)

1230 (4000)

1230 (4000)

IMPORTANT

Use the RS-423 jumper settings when communicating in RS-232
mode.