Fuses inside the inverter – Samlex America SSW-2000-12A Manuel d'utilisation

Page 16

Advertising
background image

16

Section 7 |

tRoUBLeSHootinG GUiDe

SECTION 8 |

FUSE REPLACEMENT

TROUBLE / SYMPTOMS

POSSIBLE CAUSE(S)

SUGGESTED REMEDIES

NO AC OUTPUT
On the inverter
• Green LED on the front panel of the

inverter is oN

• Red LED is OFF
• Buzzer alarm is OFF
• Yellow LED is ON

On the Remote Control SSW-R1-12B
(For SSW-1000-1500-2000-12A)
• DC input voltage is being displayed and

has risen to High DC Input Voltage Shut-
down Threshold of 15.3V +/- 0.3V

• Message “Input Fault” is flashing
• Power Bar Graph is OFF
• LCD is dimmed

Shutdown due to high DC input voltage
DC input voltage has risen to High DC Input
Voltage Shutdown Threshold of 15.3V +/- 0.3V

1. Switch off the AC load and the inverter.
2. Disconnect the DC input to the inverter
3. Check the output voltages of the battery and

charging source and ensure these are below
the High DC Input Voltage Shutdown Thresh-
old of 15.3V +/- 0.3V

4. Check that a 24V battery is not being used

instead of 12V battery

5. The unit will reset automatically once the

voltage drops to 14.9V +/- 0.2V

6. CAUTION! Voltage input of > 16 V will perma-

nently damage the inverter

INVERTER DOES NOT SHUT DOWN
WHEN REMOTE CONTROL SSW-R1-12B IS
SWITCHED OFF
(For SSW-1000-1500-2000-12A)

The ON / OFF switch on the inverter is
in ON condition

When using the remote Control SSW-r1-12b,
ensure that the oN / off switch on the inverter
is in off position

MOTORIZED POWER TOOL
WILL NOT START

excessive start-up current from the load is acti-
vating the Soft Start Circuit and is reducing the
output voltage and consequently the current
to a level where the starting torque required
by the motor is not sufficient to turn the motor.
(Starting torque in a motor is proportional to
Voltage and the Current)

If appliance does not start, then the appliance
is drawing excessive power and will not work
with the inverter

MOTORIZED POWER TOOL DOES
NOT OPERATE AT CORRECT SPEED

Purely inductive load with higher reactive
power and lower Power factor is activating the
soft start circuitry and reducing the output volt-
age resulting in reduced speed

Make the load not purely inductive. operate
an incandescent lamp at the same time as the
motor. This will reduce the reactive power and
raise the Power factor so that the Soft Start
Circuit is not activated

FUSES INSIDE THE INVERTER

The AC side of this inverter is protected by an integral electronic overload circuit and will automatically reset in some cases.

More than that, this inverter is equipped with a DC side fuses that are located inside the inverter.

Normally, these fuses will not blow unless a serious problem occurs.

Please Do NoT replace the fuses yourself. We recommend you contact technician to find and fix the

problems. High voltage and high temperature inside!

CAUTION: NO USER-SERVICEABLE COMPONENTS INSIDE. DO NOT ATTEMPT TO OPEN THE

INVERTER.