15

Section 7 |

tRoUBLeSHootinG GUiDe

TROUBLE / SYMPTOMS

POSSIBLE CAUSE(S)

SUGGESTED REMEDIES

AC OUTPUT IS AVAILABLE
On the inverter
• Green LED on the front panel of the

inverter is oN

• Red LED is OFF
• Buzzer alarm sounds intermittently when

DC input voltage drops to Low DC Input
Voltage Alarm Threshold of 11V +/- 0.3V
when delivering high power loads

• Yellow LED comes ON when buzzer

alarm is sounded.

On the Remote Control SSW-R1-12B
(For SSW-1000-1500-12A)

• DC input voltage is being displayed and

intermittently drops to Low DC Input Volt-
age Alarm Threshold of 11V +/- 0.3V when
delivering high power loads

• Message “Input Fault” intermittently

flashes whenever DC input voltage drops
to Low DC Input Voltage Alarm Threshold
of 11V +/- 0.3V

• Power Bar Graph will be ON if the output

power is > 50W to 100W

Intermittent buzzer alarm due to
intermittent high AC loads
1. DC input wire size is not adequate for higher

capacity loads or there is loose connection
between the battery and the inverter leading
to DC input voltage falling below the Low DC
Input Voltage Alarm Threshold of 11V +/- 0.3V

2. The battery has developed sulfation due to

undercharging. In this condition, the internal
resistance of the battery rises above normal
and hence causes abnormal voltage drop
on its terminals at higher discharge current
consumed by higher capacity load

1. Use thicker wires between the battery and

the inverter and tighten all DC input circuit
connections

2. Check internal resistance of the battery and

remove sulfation by equalizing the battery or
replace the battery

NO AC OUTPUT
On the inverter
• Green LED on the front panel of the

inverter is oN

• Red LED is OFF
• Buzzer alarm sounds all the time
• Yellow LED is ON

On the Remote Control SSW-R1-12B
(For SSW-1000-1500-2000-12A)
• DC input voltage is being displayed and

has dropped to Low DC Input Voltage
Shutdown Threshold of 10.5V +/- 0.3V

• Message “Input Fault” is flashing
• Power Bar Graph is OFF
• LCD is dimmed

Shutdown due to low DC input voltage
1. DC input wire size is not adequate for the

capacity of the AC load or there is loose con-
nection between the battery and the inverter
leading to DC input voltage falling below the
Low DC Input Voltage Shutdown Threshold of
10.5V +/- 0.3V

2. The battery has developed sulfation due to

undercharging. In this condition, the internal
resistance of the battery rises above normal
and hence causes abnormal voltage drop
on its terminals at higher discharge current
consumed by higher capacity load

1. Use thicker wires between the battery and

the inverter and tighten all DC input circuit
connections

2. Check internal resistance of the battery and

remove sulfation by equalizing the battery or
replace the battery

AC OUTPUT IS AVAILABLE
On the inverter
• Green LED on the front panel of the

inverter is oN

• Red LED is OFF
• Buzzer alarm sounds when DC input

voltage drops to Low DC Input Voltage
Alarm Threshold of 11V +/- 0.3V even on
low AC loads

• Yellow LED comes ON when buzzer alarm

is sounded.

On the Remote Control SSW-R1-12B
(For SSW-1000-1500-2000-12A)
• DC input voltage is being displayed and

drops to Low DC Input Voltage Alarm
Threshold of 11V +/- 0.3V even at low
loads

• Message “Input Fault” flashes whenever

DC input voltage drops to Low DC Input
Voltage Alarm Threshold of 11V +/- 0.3V

• Power Bar Graph is ON if the output

power is > 50W to 100W

Buzzer alarm due to low DC input
voltage even at low AC loads
The battery is almost discharged

recharge the battery.