3. Install the circuit breaker. Place the ON side of the

breaker over the mounting posts, as shown in Figure

4. Fasten the breaker to the module with #10-32

shakeproof screws [2] on the mounting posts and #8-

32

x

3" screws [3] and lock washers [4] through the

breaker load ends. After all screws are in place,

tighten the #10-32 screws to 27–32 in-lb and the #8-32

screws to 15–20 in-lb.

For double-branch devices, repeat this procedure for

the other breaker, as shown in Figure 5.

4. Position the breaker module. Loosen the latch lock

screws and fully retract the latches. Line up the guide

fingers on both ends of the module with the notches

in the panelboard interior rails, as shown in Figure 6.

5. Install the module. Latch one side of the circuit

breaker module. Release the rail latch. Pivot the

module onto the bus bars and engage the second

latch. Release the rail latch. Tighten the rail latch

screws to 25 in-lb, as shown in Figure 7.

Figure 4. Installing the breaker on the module.

Figure 5. Two breakers installed on the module.

Figure 6. Positioning the breaker module.

Filler

Support

#10-32 x

3

/

4

"

Hex-Head

Screw

#8-32 Screw [3] &

Lock Washer [4]

Latch Lock

Screw

Latch

Mounting

Post

#10-32

Shakeproof

Screws [2]

Filler

Support

Latch Lock

Screw

Latch