Model coding – CCI Thermal Technologies AV - Advanced Vertical Unit Heater Manuel d'utilisation

Page 7

Advertising
background image

7

MODEL CODING

Base Model

Series

Fan

Heat Exchanger

Cabinet

Motor

A 1

1 A

AH

12A

A 1 A 1

FAN SIZE

12” (305 mm) DIA

12A

16” (406 mm) DIA

16A

20” (508 mm) DIA

20A

24” (610 mm) DIA

24A

24” (610 mm) tandem

24B

A = Standard single fan

B = Standard dual fan

FAN SIZE

TUBING

W

ALL

THICKNESS

ROWS

FINNING

FINS/ INCH

MA

TERIAL

TYPE

5/8” (16 mm) .065” (1.7 mm)

3

10

AL

TW

A

1” (25 mm)

.083” (21 mm)

2

9

AL

EX

B

1” (25 mm)

.135” (3.4 mm)

2

5

AL

EX

C

TW = Tension Wound

EX = Extruded AL = Aluminum

PASSES

1 Pass

1

3 Passes

3

5 Passes

5

7 Passes

7

CONNECTIONS

1½” NPT Male Sch. 40

A

1½” (40 mm) 300# RF flange

B

2” NPT Male Sch. 80

C

2” (50 mm) 300# RF flange

D

EXCHANGER COATINGS

Heat resistant aluminum paint

1

Heresite® phenolic coating

2

CABINET MATERIAL

A

Epoxy powder coated carbon steel

B

Heresite® phenolic coated carbon steel

DISCHARGE TYPE

1

2-way aluminum louvres

2

Nozzle

3

4-way aluminum louvres

HEATER CERTIFICATION

1

General Purpose

2

X-proof Motor Only, groups C, D, E, F, & G

3

CSA Certified Heater

MOTOR ELECTRICAL

SPECIFICATIONS

VOLTS

PHASE

HERTZ

A

115

1

60

B

208

1

60

C

208

3

60

D

230

1

60

E

230

3

60

F

460

1

60

G

460

3

60

H

575

3

60

I

220

1

60

J

380

3

60

K

440

3

60

NOTE:

Ruffneck™ utilizes Doerr/Emerson/Baldor as our standard

motor. Specifying any other O.E.M. motor may result in

longer lead times. All heat exchangers are registered to CRN

OH10951.2C.

They are approved for use in all provinces and territories in

Canada.

Heresite

®

coated exchangers and cabinets: contact factory for

quote.

Louvres and fan blades are also Heresite® coated.

Contact factory for shipping lead time.

Motor designed to be used at rated voltage with tolerances of

±15%.

Motor may be marked 230V, but is suitable for 208V operation.

Tandem configuration not available on AV models.

460 1 phase motors are only certified for groups D, F & G

Only available in 16” (406 mm) and larger units

Only available in 24” (610 mm) and larger units

Built-in Disconnect only available with CSA Certified heater



D

Built-in

Disconnect

Switch