Piping applications – CCI Thermal Technologies AV - Advanced Vertical Unit Heater Manuel d'utilisation

Page 5

Advertising
background image

5

PIPING APPLICATIONS

1. For steam service use only single-pass heaters.

Refer to Model Coding Section for tube-side pass

designation.

2. Refer to figures 4-6 for typical piping applications.

3. To prevent condensate from entering the heater, slope

steam supply lines toward the steam main. In long

supply lines, drip traps may be needed.

4. For steam systems, use properly sized continuously

draining steam traps, such as float or thermostatic

types. Traps must be sized to handle start up and

operational flows.

5. If the condensate return main is above the heater

outlet or is pressurized, install a check valve after the

steam trap and a drain valve at the strainer to drain

the system during the off season.

6. Allow for efficient condensate drainage and sub-

cooling by maintaining the outlet pipe size between

the heater and steam trap. Provide at least a 10 inch

(254 mm) drop leg at condensate outlet.

7. In horizontal steam and condensate lines use

eccentric reducers only.

8. Allow for pipe expansion.

9. Eliminate pipe stress by adequately supporting all

piping. Do not rely on heater to support piping.

10. All piping must be properly sized for expected flow

rates.

11. For more piping information, consult industrial piping

handbooks.

12. Comply with all applicable piping codes.

- 5 -

Unit heater connection for

low-pressure steam,

open gravity or vacuum return system.

Unit heater connections to overhead steam

and return mains.

Unit heater connections to

overhead liquid mains

FIGURE 4

FIGURE 5

FIGURE 6

NOTES: 1. This piping arrangement is only for two-position-type control.

Modulating steam control may not provide sufficient pressure to

lift condensate to return main.

2. Do not use with fluids corrosive to steel.

3. Install using proper piping practices.

4. In horizontal pipe runs, use eccentric reducers only.

5. Use a properly sized steam trap.

NOTES: 1. For medium to high pressure systems a bucket or float trap

must be used.

2. Do not use with fluids corrosive to steel.

3. Install using proper piping practices.

4. In horizontal pipe runs, use eccentric reducers only.

5. Use a properly sized steam trap.

NOTES: 1. Do not use with fluids corrosive to steel.

2. Install using proper piping practices.

PIPING APPLICATIONS

1. For steam service use only single-pass heaters. Refer to

Model Coding Section for tube-side pass designation.

2. Refer to figures 4-6 for typical piping applications.

3. To prevent condensate from entering the heater, slope steam

supply lines toward the steam main. In long supply lines, drip

traps may be needed.

4. For steam systems, use properly sized continuously draining

steam traps, such as float or thermostatic types. Traps must

be sized to handle start up and operational flows.

5. If the condensate return main is above the heater outlet or is

pressurized, install a check valve after the steam trap and a

drain valve at the strainer to drain the system during the off

season.

6. Allow for efficient condensate drainage and subcooling by

maintaining the outlet pipe size between the heater and

steam trap. Provide at least a 10 inch (254 mm) drop leg at

condensate outlet.

7. In horizontal steam and condensate lines use eccentric

reducers only.

8. Allow for pipe expansion.

9. Eliminate pipe stress by adequately supporting all piping. Do

not rely on heater to support piping.

10. All piping must be properly sized for expected flow rates.

11. For more piping information, consult industrial piping

handbooks.

12. Comply with all applicable piping codes.

Advertising
Ce manuel est liée aux produits suivants: