3 typical through the ceiling – Napoleon Fireplaces EPA 1100 Manuel d'utilisation

Page 16

Advertising
background image

16

W415-0763 / B / 10.28.11

4.1.3 TYPICAL THROUGH THE CEILING

A.

Move the stove into position with the fl ue centered, midpoint between two
joists to prevent having to cut them. Use a plumb bob to line up the center.

B.

Cut and frame an opening in the ceiling to provide a 2” clearance between
the outside of the chimney and any combustible material. DO NOT FILL THIS
SPACE WITH ANY TYPE OF MATERIAL.


Nail headers between the joist for extra support.
Firestop spacers must be placed on the bot-
tom of each framed opening in any fl oor or
ceiling that the chimney passes through.
If your chimney system is enclosed within
the attic area, a rafter radiation shield is
required.

C.

Hold a plumb bob from the underside of
the roof to determine where the opening in
the roof should be. Cut and frame the roof
opening to maintain proper 2” clearances.

NOTE: The chimney must be supported at the ceiling or roof so that it’s
weight does not rest on the appliance and must comply with it’s
manufacturer’s instructions.

60.1A

HEADERS

FIRESTOP SPACER -
UNDERSIDE OF JOIST

FLOOR

PROTECTOR

ROOF

FLASHING

STORM

COLLAR

TERMINAL

COMBUSTIBLE

WALL

MAINTAIN 2”

CLEARANCE

CHIMNEY

CONNECTOR

CHIMNEY

SUPPORT

LISTED CHIMNEY

INSULATION

CEILING

SUPPORT

LISTED

CHIMNEY

SPECIFIED

CLEARANCE

TO STOVE

CONNECTION

DETAIL