Maintain these minimum clearances to combustibles from appliance and vent surfaces:
Appliance framing:
Non- Combustible Appliance fi nishing:
Front -

0" (0mm) to sides of appliance opening

-

0" (0mm) above appliance opening

Combustible Appliance fi nishing:

-

50" (1270mm) from bottom of appliance to enclosure top

-

3" (76mm) to top of vent pipe*

-

2" (51mm) to sides and bottom of vent pipe*

Non-combustible fi nishing material (ie. cement board, brick, stone, tile) must be used to fi nish around the
front of the appliance.

It is best to frame your appliance after it is positioned and the vent system is installed.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor
materials, i.e. tile, carpeting and hard wood.

*HORIZONTAL VENT SECTIONS:

A minimum clearance of 3” (76mm) to the top and 2” (51mm) to the sides

and bottom of the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections within
enclosures require a minimum clearance of 3” (76mm) at the top of the vent pipe, see “MINIMUM CLEARANCE
TO COMBUSTIBLE ENCLOSURES” section. Use fi restop assembly W010-2985.

*VERTICAL VENT SECTIONS:

A minimum of 2” (51mm) all around the vent pipe on all vertical runs to

combustibles is required except for clearances in appliance enclosures. Vertical vent sections within enclosures
require a minimum clearance of 2” (51mm) around the vent pipe. Use fi restop spacer W010-2985.

!

WARNING

RISK OF FIRE!

IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING

IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE

APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH

ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO

COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.

DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN

AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH

SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK

OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE

INSULATION AND OTHER MATERIALS ARE SECURED.

WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS

LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS

CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,

OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING

ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE

FURNACE AT 1382° F (750°C) AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE

MATERIALS.

MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD

COULD RESULT.

THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE

BASE.

IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, OR SPECIFIED IN THE

INSTALLATION INSTRUCTIONS. THEY MUST BE INSTALLED.

FINISHING MUST BE DONE USING A NON-COMBUSTIBLE MATERIAL PLACED FLUSH WITH THE

FRONT FACE OF THE UNIT AND EXTENDING FROM THE TOP OF THE UNIT SUCH AS

CEMENT BOARD, CERAMIC TILE, MARBLE, ETC. DO NOT USE WOOD OR DRYWALL.

ANY FIRE RATED DRYWALL IS NOT ACCEPTABLE.

71.1B

5.0 FRAMING