3.2 TYPICAL VENT INSTALLATIONS

When venting, the horizontal run must be kept
to a maximum of 20 feet (6m). If a 20 foot (6m)
horizontal run is required, the appliance must have
a minimum vertical rise off the appliance of 57"
(1448mm).

On all horizontal vent runs, ensure that the vent pipe does not slope downward.

When terminating vertically, the vertical rise is a
minimum 36"(914mm) and a maximum 40 feet
(12m) above the appliance.

40 FT

(12m)

MAX

36"

(914mm)

MIN

16" MIN

(406mm)

43" (1092mm)

MIN PLUS

RISE*

24" (610mm)

MAX

* See "VENTING" section.

43" (1092mm)