27

W415-0434 / G / 08.08.11

* The top header must be steel. The sides studs must be steel.

** The fi rst 10 inches of fi nishing material above the appliance and the fi rst 3 inches from the sides of the appliance must
be non-combustible.

*** HORIZONTAL VENT SECTIONS: A minimum clearance to combustibles of 2” is required all around the vent pipe
for the fi rst 24” of horizontal vent run. Use fi restop spacer assembly W500-0292

(supplied). The fi rst 2 feet of outer 7

inch diameter vent pipe from the appliance must be wrapped in the 1” thick insulation sleeve (supplied). Make sure the
insulation is pulled down tight to the appliance when installed. There must be a 1 inch air gap in addition to the insulation
sleeve.

*** VERTICAL VENT SECTIONS:

A minimum of 1” all around the vent pipe on all vertical runs to combustibles

is required except for clearances in appliance enclosures. Use fi restop spacer W500-0096 (not supplied).

5.1 MINIMUM CLEARANCE TO COMBUSTIBLES

Combustible framing

- 0” to stand-offs (rear only)

Non-combustible framing*

- 0” to stand-offs (top and sides only)

Combustible fi nishing

- 0” to bottom edge of the appliance

Non-combustible fi nishing**

- 10” to top edge of the appliance

- 3” to side edges of the appliance

Enclosure

top

-

19

1/2”

Vent pipe***

- 2” to top, sides and bottom

Recessed depth

- 18 1/4”

Ceiling

-54”

from

bottom

of

appliance

40

1 /8

"

37

3 /4

" 56

3 /4

"

INSIDE
CHASE

OUTSIDE CHASE

4

"

6

"

4

"

2”

2”

0”

37

3

/4

"

18

1

/4

"

18

1

/4

"

37

3

/4

"