Specifications, Ordering information – Honeywell F300E Manuel d'utilisation

Page 2

Advertising
background image

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

68-0240EF—3

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your Total Comfort System wholesaler or distributor, refer to the Total Comfort

System catalog or price sheets for complete ordering number or specify:

1.

Order number.

2.

Voltage and frequency.

3.

Dimensions: 16 x 20 in. (406 x 508 mm), 16 x 25 in. (406 x 635 mm), 20 x 20 in. (508 x 508 mm) and 20 x 25 in.

( 508 x 635 mm),

4.

Conversion Kit for changing two-cell 120V, 60 Hz models to 240V, 60 Hz or 220/240V, 50 Hz.

5.

W8600F Air Cleaner Monitor, if desired.

6.

W8600A AIRWATCH™ Indicator, if desired.

7.

Additional F300 Electronic Air Cleaner Media Postfilters, as needed.

If you have additional questions, need further information, or would like to comment on our products or services, please:

1.

Write: Automation and Control Solutions Customer Response, 1985 Douglas Drive N, Golden Valley, MN 55422-4386.

2.

Visit our web site: www.honeywell.com/yourhome.

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not

include normal manufacturing tolerances. Therefore,

this unit may not exactly match the listed specifica-

tions. This product is tested and calibrated under

closely controlled conditions, and some minor differ-

ences in performance can be expected if those con-

ditions are changed.

Model:

Electronic Air Cleaner: Includes cabinet, access door, solid

state power supply, two electronic cells, two metal mesh

prefilters, and two media postfilters.

Electrical Ratings:

Voltage and Frequency: Models available for 120V, 60 Hz.

Can be converted in the field to 240V, 60 Hz or 220/240V,

50 Hz with the 203365A Conversion Kit.

Power Consumption: 36W maximum.

Current Draw: See Table 1.

Ionizer Voltage: 8150 Vdc.

Collector Voltage: 4075 Vdc.

Fractional Efficiency:

Efficiency ratings are based on American Society of Heating,

Refrigerating and Air-Conditioning Engineers Standard

52.2-1999. Efficiency ranges are defined for small particles,

E

1

=.3 to 1.0 micron; medium particles, E

2

= 1.0 to 3.0

microns; and large particles, E

3

= 3.0 to 10.0 microns.

E

1

= Up to 81% at 492 fpm.

E

2

= Up to 93% at 492 fpm.

E

3

= Up to 99% at 492 fpm.

Pressure Drop Vs. Airflow:

Temperature Ratings:

Operating Ambient: 40° to 125°F (4° to 52°C).

Temperature of Airflow Through Cells: 40° to 125°F

(4° to 52°C).

Maximum Cell Washing Temperature: 220°F (140°C).

Storage and Shipping Ambient: Minus 40°F to plus 140°F

(minus 40°C to plus 60°C).

Mounting:

Mounts in the return air duct of a forced air heating, cooling, or

ventilating system. Mount upstream from an atomizing

humidifier. See Planning the Installation section.

Weight:

See Table 2.

Dimensions:

See Fig. 1.

Approvals:

Underwriters Laboratories Inc. Listed: File E30954.

Table 1. Current Draw.

Size

No.

Cells

Max Current (A)

in.

mm

120V

220/240V

16 x 25

406 x 635

2

0.4

0.2

20 x 25

508 x 635

2

0.4

0.2

16 x 20

406 x 508

2

0.4

0.2

20 x 20

508 x 508

2

0.4

0.2

Velocity (fpm)

Pressure Drop (in.wc)

123.0

0.030

246.0

0.086

295.0

0.112

369.0

0.165

492.0

0.266

615.0

0. 402

Advertising