Rockwell Automation 1771-IFMS Intrinsically Safe Fast Millivolt Input Module User Manual Manuel d'utilisation
Page 42

Publication 1771-6.5.119
A-2 Specifications
Wiring arm
1771-WG
Field Wiring Arm Screw
Torque
0.8…1.0 Nm (7…9 lb•in)
Enclosure Type Rating
None (open-style)
North American Temp
Code
T6
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications
Attribute
Value
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
Non-Operating
Temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
15 g
Non-Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD Immunity
IEC 61000-4-2:
6 kV indirect contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4:
±1 kV at 5 kHz on signal ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Intrinsically Safe Fast Millivolt Input Module - 1771-IFMS
Attribute
Value