Rockwell Automation 1771-IFMS Intrinsically Safe Fast Millivolt Input Module User Manual Manuel d'utilisation

Page 42

Advertising
background image

Publication 1771-6.5.119

A-2 Specifications

Wiring arm

1771-WG

Field Wiring Arm Screw
Torque

0.8…1.0 Nm (7…9 lb•in)

Enclosure Type Rating

None (open-style)

North American Temp
Code

T6

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications

Attribute

Value

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)

Non-Operating
Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
15 g

Non-Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
6 kV indirect contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4:
±1 kV at 5 kHz on signal ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Intrinsically Safe Fast Millivolt Input Module - 1771-IFMS

Attribute

Value

Advertising