Ground the module, Chassis ground, Ground the module -8 – Rockwell Automation 1771-IFMS Intrinsically Safe Fast Millivolt Input Module User Manual Manuel d'utilisation
Page 20: Chassis ground -8

Publication 1771-6.5.119
2-8 Install the Module
Ground the Module
When using shielded cable wire, ground the foil shield and drain wire
only at on end of the cable. We recommend that you wrap the foil
shield and drain wire together and connect them to a chassis
mounting bolt. At the opposite end of the cable, tape exposed shield
and drain wire with electrical tape to insulate it from electrical contact.
Refer to the Industrial Automation Wiring and Grounding Guidelines,
Chassis Ground
When you connect grounding conductors to the chassis grounding
stud, place a star washer under the first lug, then place a nut with a
captive lock washer on top of each ground lug.
20104-M
Remove a lenght of cable
jacket from the cable.
Pull the foil shield and bare drain
wire from the insulated wires.
Bare drain
wire
Insulated
wires
Foil shield
Twist the foil shield and drain
wire together to form a single
strand.
Attach a ground lug.
19480