Publication 1769-IN028B-EN-P - October 2008

North American Hazardous Location Approval

Install Safety Circuits

Circuits that are installed on the machine for safety reasons, like overtravel limit switches, stop
push buttons, and interlocks, should always be hard-wired directly to the master control relay.
These devices must be wired in series so that when any one device opens, the master control
relay is de-energized, thereby removing power to the machine.

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet
équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of
the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the
time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.

WARNING

EXPLOSION HAZARD -

• Do not disconnect equipment

unless power has been removed
or the area is known to be
nonhazardous.

• Do not disconnect connections to

this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.

• Substitution of components may

impair suitability for Class I,
Division 2.

• If this product contains batteries,

they must only be changed in an
area known to be nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION –

• Couper le courant ou s'assurer

que l'environnement est classé
non dangereux avant de
débrancher l'équipement.

• Couper le courant ou s'assurer

que l'environnement est classé
non dangereux avant de
débrancher les connecteurs. Fixer
tous les connecteurs externes
reliés à cet équipement à l'aide
de vis, loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.

• La substitution de composants

peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.

• S'assurer que l'environnement est

classé non dangereux avant de
changer les piles.

WARNING

Explosion Hazard - Do not connect or disconnect connectors while circuit is live.

ATTENTION

Never alter these circuits to defeat their function. Serious injury or machine damage
could result.