Rockwell Automation 1769-PB4 Compact I/O Expansion Power Supplies Manuel d'utilisation

Page 31

Advertising
background image

Compact I/O Expansion Power Supplies 31

Publication 1769-IN028B-EN-P - October 2008

Wire size

2.5 mm

2

(14 AWG) solid copper wire rated at 90 °C (194 °F), or greater, 1.2 mm

(3/64 in.) insulation max

North American
temp code

T3C

IEC temp code

N/A

T4

N/A

T4

Enclosure type
rating

None (open style)

(1)

When configuring your system using a MicroLogix 1500 controller, only one expansion cable, one expansion power supply
and a total of eight I/O modules may be used in a maximum of two banks of I/O modules. The expansion power supply
cannot be directly connected to the MicroLogix 1500 controller.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 - Environmental Specifications

Attribute

1769-PA2

1769-PB2

1769-PA4

1769-PB4

Operating
temperature

IEC 60068-2-1 (Test
Ad, Operating Cold

IEC 60068-2-2 (Test
Bd, Operating Dry
Heat)

IEC 60068-2-14
(Test Nb, Operating
Thermal Shock)

0…60 °C (32…140 °F)

Nonoperating
temperature

IEC 60068-2-1 (Test
Ab, Unpackaged
Nonoperating Cold)

IEC 60068-2-2 (Test
Bb, Unpackaged
Nonoperating Dry
Heat)

IEC 60068-2-14
(Test Na,
Unpackaged
Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30
(Test Db,
Unpackaged Damp
Heat)

5…95% noncondensing

1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 - Technical Specifications

Attribute

1769-PA2

1769-PB2

1769-PA4

1769-PB4

Advertising