8 ArmorBlock MaXum 4 Output Module Series B
Publication 1792D-IN040B-EN-P - September 2000
Communicate with Your ArmorBlock MaXum I/O
Module
This ArmorBlock module’s I/O is exchanged with the master through
a cyclic, poll, or change-of-state connection.
The module consumes and produces output data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. This 4 output module consumes the
message, updates outputs, and produces a response. The response
has output faults and contains the status of the Auxiliary power.
Change-of-State - productions occur when an output changes or a
fault condition occurs. If no output or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate.
Refer to the table below for the word/bit definitions.
Type of I/O Connections
Consumes
Produces
Cyclic
1 Bytes
1 Byte
Polled
1 Bytes
1 Byte
Change-of-State
1 Bytes
1 Byte
Bit
07
06
05
04
03
02
01
00
Produces 0
RSVD
OPWR
RSVD
RSVD
OFLT3
OFLT2
OFLT1
OFLT0
Consumes 0
RSVD
RSVD
RSVD
RSVD
O3
O2
O1
O0
Where: RSVD = Reserved OPWR = Output Power (Auxiliary Power) OFLT = Output Fault O = Output
Byte
Bit
Description
Produces 0
00-03
04-05, 07
06
Output no load or overload fault (OFLT): - When the bit is set
(1), an output fault has occurred. OFLT0=outpout 0,
OFLT1=output 1, OFLT2=output 2, OFLT3=output 3.
Reserved
Output Power Fault (OPWR): When the bit is set (1),
Auxiliary Power is not present.
Consumes 0
00-03
04-07
Output bits: When the bit is set (1), the output will be turned
on. Bit 00=output 0, bit 01=output 1, bit 02=output 2, bit
03=output 3
Reserved