The following table describes network and module status indicators.

The following table describes logic status indicators.

The following table describes Auxiliary power indicator.

The following table describes I/O status indicators.

Net/Mod Status Indicator

Indicator

Status

Off

No power or auto bauding

Flashing Green/Off On line but not connected

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - module configuration error

I/O connection fault - one or more I/O connections in the timed-out state

Solid Red

Unrecoverable fault

Communication failure - duplicate node address present or incorrect
baud rate

Green to Red to Off At powerup only - LED test

Logic Status Indicators

State

Status

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

Auxiliary Power

Indication

Status

None

No Auxiliary Power

Green

Solid

Auxiliary Power Present

I/O Status Indicators

Function

Module Status Indicator

Point Indicator

Condition

Outputs

Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red

None
Yellow
Orange
Red
Orange
Red

Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching