Connect the output cord sets to the maxum module – Rockwell Automation 1792D-OB4D ArmorBlock MaXum 4 Output Module Series B Manuel d'utilisation
Page 6

6 ArmorBlock MaXum 4 Output Module Series B
Publication 1792D-IN040B-EN-P - September 2000
Connect the Output Cord Sets to the MaXum Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the connectors on your module. Remove the
caps and connect your cord sets to the appropriate ports.
Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown below.
Please refer to publication 889-5.0 for Rockwell Automation cables
and cord sets offerings.
ATTENTION
!
• Make sure all connectors and caps are securely
tightened to properly seal the connections
against leaks and maintain IP67 requirements.
• For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should be
connected together.
• I/O cable length should be less than 30 meters.
1
5
3
4
2
Micro-Connector
(View into Sockets)
Pin 1 Not Used
Pin 2 Not Used
Pin 3 Auxiliary Power Ground
Pin 4 Output
Pin 5 Not Used
41452