Output specifications relay contact ratings – Rockwell Automation 1769-IQ6XOW4 Compact Combination 24V dc Sink/Source Input AC/DC Relay Output Module Manuel d'utilisation
Page 17

Compact™ Combination 24V dc Sink/Source Input & AC/DC Relay Output Module 17
Publication 1769-IN050A-EN-P - April 2001
Output Specifications
Relay Contact Ratings
Specification
1769-IQ6XOW4
Voltage Category
AC/DC normally open relay
Operating Voltage Range
5 to 265V ac
5 to 125V dc
Number of Outputs
4
Signal Delay (max.) – resistive load
turn-on = 10 ms
turn-off = 10 ms
Off-State Leakage (max.)
0 mA
On-State Current (min.)
10 mA at 5V dc
Continuous Current per Point (max.)
2.5A (Also see “Relay Contact Ratings” on page 17.)
Continuous Current per Common (max.)
8A
Volts (max.) Continuous Amps per
Point (max.)
Amperes
(1)
(1)
Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
Voltamperes
NEMA
ICS 2-125
Make
Break
Make
Break
240V ac
2.5A
7.5A
0.75A
1800 VA
180 VA
C300
120V ac
15A
1.5A
125V dc
1.0A
0.22A
(2)
(2)
For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 48V, the make/break ratings
for relay contacts cannot exceed 2A.
28 VA
R150
24V dc
2.0A
1.2A
28 VA
—