Output specifications relay contact ratings – Rockwell Automation 1769-IQ6XOW4 Compact Combination 24V dc Sink/Source Input AC/DC Relay Output Module Manuel d'utilisation

Page 17

Advertising
background image

Compact™ Combination 24V dc Sink/Source Input & AC/DC Relay Output Module 17

Publication 1769-IN050A-EN-P - April 2001

Output Specifications

Relay Contact Ratings

Specification

1769-IQ6XOW4

Voltage Category

AC/DC normally open relay

Operating Voltage Range

5 to 265V ac
5 to 125V dc

Number of Outputs

4

Signal Delay (max.) – resistive load

turn-on = 10 ms
turn-off = 10 ms

Off-State Leakage (max.)

0 mA

On-State Current (min.)

10 mA at 5V dc

Continuous Current per Point (max.)

2.5A (Also see “Relay Contact Ratings” on page 17.)

Continuous Current per Common (max.)

8A

Volts (max.) Continuous Amps per

Point (max.)

Amperes

(1)

(1)

Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.

Voltamperes

NEMA
ICS 2-125

Make

Break

Make

Break

240V ac

2.5A

7.5A

0.75A

1800 VA

180 VA

C300

120V ac

15A

1.5A

125V dc

1.0A

0.22A

(2)

(2)

For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 48V, the make/break ratings
for relay contacts cannot exceed 2A.

28 VA

R150

24V dc

2.0A

1.2A

(2)

28 VA