Rockwell Automation 1769-IQ6XOW4 Compact Combination 24V dc Sink/Source Input AC/DC Relay Output Module Manuel d'utilisation
Page 10

10 Compact™ Combination 24V dc Sink/Source Input & AC/DC Relay Output Module
Publication 1769-IN050A-EN-P - April 2001
2. Route the wire under the terminal pressure plate. You can use the bare wire
or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening screws is 0.68 Nm (6 in-lbs).
Simplified Input Circuit Diagram
Simplified Output Circuit Diagram
TIP
The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [maximum 1/4 inch o.d. with
a 0.139 inch minimum i.d. (M3.5)] with the module.
TIP
If you need to remove the finger-safe cover, insert a
screw driver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be
able to put it back on the terminal block because the
wires will be in the way.
3K
Vcc
IN
DC COM
536
0.1
µ
F
+24V
VAC- VDC
OUT