Installation continued – Garland XG36 GAS XPRESS GRILL Manuel d'utilisation

Page 7

Advertising
background image

Part # 4517124 Rev. 7 (08/17/11)

Page 7

INSTALLATION continued

Grill is to be located directly under ventilation system.

Once installed in the grill station underneath the ventilation

system, the platens, in their highest position, must not

interfere with the lower lip of the ventilation system hood.

The raised position of each platen is adjusted by raising

or lowering the upper of the two microswitches, (limit

switches), in the rear of the grill. The lower microswitch

position must not be adjusted.

Grill plate must be level front to back, side to side and

diagonally. This leveling must be done with the unit under

the hood and in it’s normal operational position to prevent

warping of the grill plate.

NOTE: Fuses are installed to prevent damage in the event of

failure of the upper microswitch.

Installation shall be made with the gas connector that has

been supplied loose with the grill. The quick disconnect

fitting and gas shut off valve must be installed in the

direction indicated on their outer body.

NOTE: When checking gas pressure, be sure that all other

equipment on the same gas line is on.

The appliance and its individual shut-off valve must be

disconnected from the gas supply piping system during any

pressure testing of that system pressures in excess of ½ PSIG

(3.45kPa).

Adequate clearance must be provided for servicing and

proper operation.

National Codes Requirements:

The type of gas for which the grill is equipped is stamped on

the data plate on the inside rear of the unit and on the lower

front panel. Connect a grill stamped for Natural Gas only to

Natural Gas.

The installation must conform to the National Fuel Gas Code

ANSI Z223.1-1998 or latest edition, NFPA No. 54 – latest

edition and National Electrical Code ANSI/NFPA 70-1990 or

latest edition and/or local code to assure safe and efficient

operation. In Canada, the installation must comply with CSA

B149.1 and local codes where applicable

In Canada, electrical connection must comply with

applicable sections of the Canadian Electrical Code, C22.1

- 1990, latest edition, “Safety Standard for Installation,

Part 1” and C22.2- No. O-M 1982 latest edition , “General

Requirements, Part 2”.

Gas Connections, and Pipe Sizing:

The size of the gas line is very important. If the line is too

small, the gas pressure at the burner manifold will be low.

This will cause slow recovery and delayed ignition. The

incoming gas pressure line should be a minimum of 1-1/2".

All grills require a 3/4" connection.

Before connecting new pipe the pipe must be blown out to

dispose of any foreign particles. These particles will cause

improper operation.

When using thread compound, use small amounts on male

threads only. Use a compound that is not affected by the

chemical action of LP gases. Avoid applying compound

to the first two threads to prevent clogging of the burner

orifices and control valve.

Have the installer check all gas plumbing with a soap

solution for leaks. DO NOT USE matches, candles or other

ignition sources in checking for leaks.

The grill must be disconnected from the gas supply system

when pressure testing of that system at pressures in excess

of 2 psi.

Check the data plate to determine the proper type of gas

before connecting the quick disconnect or piping from the

building gas supply.

An incoming gas pressure test nipple is provided on the

incoming gas manifold for pressure checks.

Minimum incoming gas pressure for Natural Gas is 6" W.C.

Maximum incoming gas pressure for Natural Gas is 14" W.C.

Minimum incoming gas pressure for Propane is 10" W.C.

Maximum incoming gas pressure for Propane is 26" W.C.

Burner operating gas pressure can be checked at the outlet

side of the gas valve at the pressure test point.

Burner manifold pressure for Natural Gas must be 3.5" W.C.

Burner pressure for Propane must be 3.5" W.C.

To adjust the burner pressure, remove the sealing screw

from the pressure test nipple, connect a manometer, remove

the sealing cap on the gas valve regulator, turn on the grill,

adjust the screw in the regulator to give the correct pressure,

turn off the grill, refit the regulator sealing cap, remove the

manometer, replace the seal screw in the test nipple and test

for gas leaks.

Gas pressures should be checked by the local Gas Company

or an authorized service agency only.

Test all piping and connections for gas leaks. A rich soap

solution should be used for this purpose. Never use a flame.

Advertising
Ce manuel est liée aux produits suivants: